Resistance In Wire Calculator

Choose the wire material and gauge, enter the one-way length and the current, and press the button. The tool works out the wire resistance from resistivity, length and area, then the voltage drop and the power lost, for the one-way run and for the round trip.

Resistivity values are at 20 °C. Round-trip figures double the one-way length, because current travels out along one conductor and back along the other. This calculator is for planning and education only: it gives DC resistance and voltage drop for a plain conductor, and it does not check whether a wire size, installation or load follows local electrical codes. Your entries stay in your browser.

A resistance in wire calculator works out how much a length of wire resists the flow of current, and how much voltage and power that resistance takes away. Enter the material, the gauge, the one-way length and the current, and it returns the wire resistance, the voltage drop for the one-way run and for the round trip, and the power lost in the wire as heat.

How do I use the Resistance In Wire Calculator?

Choose the wire material first. Copper is the default, because it is the most common conductor in wiring; aluminium, silver, gold, iron and nichrome are also listed, each with its resistivity at 20 °C shown beside the name. Then choose the gauge. The list runs from 24 AWG, a thin wire, up to 4/0 AWG, a thick cable, and the tool works out the cross-sectional area from the gauge for you. If the wire is not an AWG size — for example a metric cable sold by square millimetres — choose Custom area and type the area in mm² instead.

Enter the one-way wire length in metres: the distance from the supply to the load along one conductor. Enter the current in amperes: the current the load draws. The supply voltage is optional. If you enter it, the tool also shows the voltage drop as a percentage of the supply and the voltage that reaches the load. If you leave it blank, those two boxes show a dash and the rest of the results still appear.

Press the calculate button and eight labelled boxes appear. The first shows the cross-sectional area the tool used. The second and third show the wire resistance for the one-way run and for the round trip. The fourth and fifth show the voltage drop for the one-way run and for the round trip. The sixth shows the round-trip drop as a percentage of the supply voltage, when a supply voltage was entered. The seventh shows the power lost in the wire in watts. The eighth shows the voltage that reaches the load. Under the boxes, a note repeats the material and resistivity used, the length and current entered, and whether the round-trip figures doubled the length.

If an input is wrong, the tool shows a plain-language error and no results. A length of 0 or a negative length is rejected, because a wire with no length has no resistance to calculate. A custom area of 0 or below is rejected for the same reason. A blank length, blank current or blank custom area is rejected with a message naming the box. A negative current is rejected, and a supply voltage of 0 or below is rejected when one is entered. A current of 0 is accepted: a wire carrying no current drops no voltage and loses no power, so the tool returns a drop of 0.000 V and a power loss of 0.00 W, with the resistance figures unchanged.

Designed illustration of a copper wire cross-section with glowing current, showing a wire resistance of 0.1015 ohms, a voltage drop of 0.508 V, and power lost of 2.54 W.

What does a worked example look like?

Start with the first test: a copper wire, 12 AWG, 10 m long, carrying 5 A from a 120 V supply. The tool works out the cross-sectional area of 12 AWG as 3.3088 mm². The resistance of the one-way run is 0.0508 ohms, and the round-trip resistance is 0.1015 ohms. The voltage drop on the one-way run is 0.254 V, and the round-trip drop is 0.508 V, which is 0.42% of the 120 V supply. The power lost in the wire is 2.54 W, and the voltage that reaches the load is 119.49 V. The drop is small here because the wire is short, thick and lightly loaded.

A second test changes the material, the gauge, the length and the load together: an aluminium wire, 14 AWG, 25 m long, carrying 10 A from a 240 V supply. The area of 14 AWG is 2.0809 mm². The one-way resistance is 0.3388 ohms and the round-trip resistance is 0.6776 ohms. The one-way drop is 3.388 V and the round-trip drop is 6.776 V, which is 2.82% of the 240 V supply. The power lost is 67.76 W, and the voltage at the load is 233.22 V. The drop is larger than in the first test for three reasons that stack: aluminium resists more than copper, the wire is longer, and the current is twice as large.

A third test shows what happens when the wire is thin and the run is long: a copper wire, 24 AWG, 100 m long, carrying 0.5 A from a 12 V supply. The area of 24 AWG is only 0.2047 mm². The one-way resistance is 8.2059 ohms and the round-trip resistance is 16.4118 ohms. The one-way drop is 4.103 V and the round-trip drop is 8.206 V, which is 68.38% of the 12 V supply. The power lost is 4.10 W, and only 3.79 V reaches the load. A 12 V load fed through this wire would see less than a third of its supply voltage, which is why thin wire over a long run is a poor match for a low-voltage load.

A fourth test uses the custom area option: a nichrome wire with a cross-sectional area of 1.0000 mm², 5 m long, carrying 2 A from a 230 V supply. The one-way resistance is 5.5000 ohms and the round-trip resistance is 11.0000 ohms. The one-way drop is 11.000 V and the round-trip drop is 22.000 V, which is 9.57% of the 230 V supply. The power lost is 44.00 W, and the voltage at the load is 208.00 V. Nichrome resists far more than copper — its resistivity is about 65 times higher — so even a short length drops a large voltage, which is exactly why nichrome is used in heating elements rather than in wiring.

How does the maths behind wire resistance work?

The resistance of a uniform wire follows one formula: R = ρL/A. R is the resistance in ohms, ρ (rho) is the resistivity of the material in ohm-metres, L is the length in metres, and A is the cross-sectional area in square metres. The formula says three things in plain terms. A longer wire resists more, because the current has further to travel. A thicker wire resists less, because there is more material for the current to pass through. And a material with a higher resistivity resists more at the same length and area.

Resistivity is a property of the material itself, not of the wire's size. The table below lists the six materials in the tool, with the resistivity values the tool uses at 20 °C. The figures come from published resistivity tables, and the same six figures appear in the tables reproduced by Physics LibreTexts, Engineering ToolBox and wutools.

MaterialResistivity at 20 °C (Ω·m)Where it is used
Silver1.59 × 10⁻⁸Contacts and specialised electronics
Copper1.68 × 10⁻⁸General wiring, the most common conductor
Gold2.44 × 10⁻⁸Connector plating, corrosion-resistant contacts
Aluminium2.82 × 10⁻⁸Overhead lines and larger cables
Iron9.71 × 10⁻⁸Cores and structural parts, not wiring
Nichrome1.10 × 10⁻⁶Heating elements, resistors

Silver is the best conductor in the table, but it is rarely used for wiring because of its cost. Copper is the practical choice for most wiring: it is the second-best conductor and far cheaper than silver. Gold resists more than copper, and it is used where corrosion resistance matters, such as connector plating, rather than for carrying current over distance. Aluminium resists about 68% more than copper at the same gauge, because 2.82 divided by 1.68 is 1.68, so an aluminium wire needs a larger area to match a copper wire's resistance. Iron resists about 5.8 times as much as copper, and nichrome about 65 times as much, which is why neither is used for ordinary wiring.

The units need care, because the formula only works when the units agree. Resistivity is in ohm-metres, length is in metres, and area must be in square metres. Wire areas are usually stated in square millimetres, and one square millimetre is 0.000001 square metres, so the tool converts the area before applying the formula. The AWG diameters come from the standard AWG formula, d = 0.127 × 92^((36 − n)/39) millimetres, where n is the gauge number, and the area from A = πd²/4. For 12 AWG that gives a diameter of 2.053 mm and an area of 3.3088 mm², which is the area the first worked example uses. If you enter the wrong unit — for example, typing the area in square centimetres where square millimetres were expected — the answer will be wrong by a factor of 100, so check the unit label on each box before pressing calculate. The electrical unit converter can help with unit changes.

Once the resistance is known, the rest follows from Ohm's law, V = I × R. The voltage drop across the wire is the current multiplied by the wire's resistance, and the power lost in the wire is the current squared multiplied by the resistance, P = I² × R. The power loss grows with the square of the current: doubling the current doubles the voltage drop but quadruples the power lost. That is why a wire that is warm at 5 A can be hot at 10 A, and why the current matters more than the length when the power loss is the question. If you already know a resistance value and want the other electrical values, the Ohms Law Calculator takes any two of voltage, current, resistance and power and solves for all four.

What is voltage drop, and why does the round trip matter?

Voltage drop is the voltage used up by the wire itself between the supply and the load. A wire is not a perfect conductor: it has resistance, and when current flows through that resistance, some voltage is lost along the way. The load then receives the supply voltage minus the drop. In the first worked example the supply is 120 V and the drop is 0.508 V, so the load receives 119.49 V. In the third worked example the supply is 12 V and the drop is 8.206 V, so the load receives only 3.79 V.

The round trip matters because current travels out to the load along one conductor and back to the supply along another. Both conductors have resistance, so the total resistance in the path is twice the resistance of one length. A common mistake is to calculate the drop for the one-way length only and forget the return conductor, which gives half the real drop. The tool shows both figures so the difference is visible: in the first worked example the one-way drop is 0.254 V and the round-trip drop is 0.508 V, exactly twice as much. For a single-wire earth-return path the one-way figure may be the right one, but for an ordinary two-conductor circuit the round-trip figure is the one to compare against the supply.

The drop as a percentage is the round-trip drop divided by the supply voltage, multiplied by 100. The percentage is what the usual guidance is written in, and it is also the figure that shows whether a drop matters: 0.508 V is 0.42% of 120 V and is easy to ignore, while 8.206 V is 68.38% of 12 V and changes what the load receives. The same drop in volts means very different things at different supply voltages, which is why the tool asks for the supply voltage when you want the percentage.

How much voltage drop is acceptable?

The National Electrical Code, the NEC, gives its voltage-drop guidance in informational notes at 210.19 and 215.2: conductors sized to keep the drop to 3% on a branch circuit, and 5% in total from the service entrance to the farthest outlet, will provide reasonable efficiency of operation. Those figures are recommendations, not enforceable requirements: the notes are explanatory material under NEC 90.5(C), and the code uses "should not exceed" rather than "shall not exceed". Some local jurisdictions adopt the 3% and 5% figures as enforceable amendments, and a few specific cases, such as fire-pump circuits, do have mandatory limits, so the local rules for the installation are what govern.

In volts, the 3% and 5% figures are 3.6 V and 6.0 V on a 120 V circuit, and 7.2 V and 12.0 V on a 240 V circuit. The second worked example, an aluminium 14 AWG wire over 25 m at 10 A, drops 6.776 V on a 240 V supply, which is 2.82%: inside the 3% branch-circuit figure. The iron example in the limits section drops 11.871 V on a 24 V supply, which is 49.46%: far past any of these figures, and a load fed that way would receive only 12.13 V of its 24 V.

The voltage-drop table in the next section shows the 3% line being crossed as current rises, using the same copper wire at the same length. At 15 A on 12 AWG over 30 m, the drop is 4.570 V, which is 3.81% of 120 V — past the 3% branch-circuit figure. At 10 A the same wire drops 3.046 V, which is 2.54% — inside it. The wire did not change; the current did. That is the practical use of this calculator: find the current at which the drop crosses the figure you are working to, and then decide whether the wire, the length or the current needs to change. This page gives no advice on which of those to change, and no advice on whether a particular installation follows local codes. It is for planning and education only, and electrical work must follow local codes and be carried out by a qualified person.

What is the resistance of copper wire by gauge?

The table below gives the resistance of copper wire by AWG gauge, per 100 metres, at 20 °C. Every figure was computed with the same formula the tool uses, R = ρL/A with copper resistivity 1.68 × 10⁻⁸ ohm-metres, from the standard AWG diameters. The diameter and area columns are included so the table can be checked by hand.

AWGDiameter (mm)Area (mm²)Resistance per 100 m (Ω)Resistance per metre (mΩ/m)
240.5110.2058.205982.06
220.6440.3265.160851.61
200.8120.5183.245632.46
181.0240.8232.041220.41
161.2911.3091.283712.84
141.6282.0810.80738.07
122.0533.3090.50775.08
102.5885.2610.31933.19
83.2648.3660.20082.01
64.11513.3020.12631.26
45.18921.1510.07940.79
26.54433.6310.05000.50
1/08.25153.4750.03140.31
4/011.684107.2190.01570.16

Two patterns in the table are worth reading. First, each step of six AWG numbers roughly quarters the resistance: 24 AWG is 8.2059 ohms per 100 m and 18 AWG is 2.0412, then 12 AWG is 0.5077, then 6 AWG is 0.1263. That is because the AWG scale is geometric: three steps double the cross-sectional area, so six steps multiply it by four and divide the resistance by four. Second, the table shows why thin wire is a poor match for a long run: 100 m of 24 AWG copper is 8.2059 ohms, while 100 m of 12 AWG is 0.5077 ohms, a factor of about 16. The third worked example uses that 24 AWG figure directly: 100 m of it is 8.2059 ohms one-way, and at 0.5 A that is a 4.103 V drop one-way and 8.206 V round-trip.

The figures in this table use copper resistivity of 1.68 × 10⁻⁸ ohm-metres at 20 °C. Published copper values vary slightly with the standard used: annealed copper under IEC 60028 is 1.724 × 10⁻⁸, which would give 0.5210 ohms per 100 m for 12 AWG instead of 0.5077. The difference is about 2.6%, and it is a difference in the published resistivity value, not in the arithmetic. Manufacturer data sheets and code tables, such as NEC Chapter 9 Table 8, give resistance at 75 °C rather than 20 °C, and resistance rises with temperature, so those figures are higher again. When a specification sheet gives a resistance per length, use that figure for the installation and use this table for comparison and planning.

How much voltage does a wire drop at different currents?

The two tables below use the same setup — a copper wire, 30 m one-way, fed from a 120 V supply — and change only the gauge and the current. Every figure was computed with the tool's own arithmetic, and the round-trip drop is the figure the NEC percentages are compared against.

Current (A)12 AWG round-trip drop (V)% of 120 VPower lost (W)Voltage at the load (V)
51.5231.27%7.62118.48
103.0462.54%30.46116.95
154.5703.81%68.55115.43
206.0935.08%121.86113.91
Current (A)14 AWG round-trip drop (V)% of 120 VPower lost (W)Voltage at the load (V)
52.4222.02%12.11117.58
104.8444.04%48.44115.16
157.2666.06%108.99112.73
209.6888.07%193.76110.31

Read the two tables together. At 10 A the 12 AWG wire drops 3.046 V, which is 2.54% and inside the 3% branch-circuit figure, while the thinner 14 AWG wire drops 4.844 V, which is 4.04% and past it. At 15 A the 12 AWG wire crosses the line too, at 3.81%. At 20 A the 12 AWG wire drops 6.093 V, which is 5.08% and past the 5% total figure as well, and the 14 AWG wire drops 9.688 V, which is 8.07%. The power lost grows faster than the drop: on 12 AWG, doubling the current from 5 A to 10 A doubles the drop from 1.523 V to 3.046 V but quadruples the power lost from 7.62 W to 30.46 W. Doubling again to 20 A gives 6.093 V and 121.86 W, which is 16 times the power lost at 5 A. To see what a total means as a share of the supply, the percentage calculator gives the figure: 6.093 V out of 120 V is 5.08%, and 9.688 V out of 120 V is 8.07%.

How do I choose between copper and aluminium?

The choice starts with resistivity. Aluminium's resistivity is 2.82 × 10⁻⁸ ohm-metres against copper's 1.68 × 10⁻⁸, so at the same gauge an aluminium wire has about 68% more resistance than a copper wire, and it drops about 68% more voltage at the same current and length. The second worked example shows this in practice: an aluminium 14 AWG wire over 25 m at 10 A drops 6.776 V round-trip. A copper 14 AWG wire of the same length and current would drop 4.037 V, which is the aluminium figure divided by 1.68. (That 4.037 V figure is the tool's arithmetic for copper 14 AWG at 25 m and 10 A: 0.8073 ohms per 100 m gives 0.2018 ohms one-way over 25 m, 0.4037 ohms round-trip, and 10 A times 0.4037 ohms is 4.037 V.)

To match a copper wire's resistance, an aluminium wire needs a larger cross-sectional area — about 68% larger, because the resistance is proportional to resistivity divided by area. That is why aluminium wiring is usually one or two gauges thicker than the copper wire it replaces. Aluminium is lighter than copper and cheaper per kilogram, which is why it is used for overhead lines and large cables, where weight and cost matter more than size. For short runs inside equipment, copper's smaller size and lower resistance usually win. This page does not recommend one material over the other for any particular installation: the choice also involves terminations, corrosion, temperature ratings and local codes, and those are outside what this calculator checks.

What mistakes do people commonly make with wire resistance?

The first mistake is using the one-way length when the circuit needs the round trip. Current travels out and back, so the resistance in the path is twice the one-way resistance. Forgetting the return conductor gives half the real drop, and a result that looks inside the 3% figure can really be past it.

The second mistake is mixing up the units. The formula needs length in metres and area in square metres, while wire areas are usually stated in square millimetres. Typing an area in square centimetres where square millimetres were expected makes the answer wrong by a factor of 100. The tool takes the area in square millimetres, and the AWG picker works the area out from the gauge, so the unit is fixed for you.

The third mistake is using the wrong resistivity. Published copper values range from 1.68 × 10⁻⁸ to 1.724 × 10⁻⁸ ohm-metres depending on the standard, and aluminium is listed as 2.82 × 10⁻⁸ in some tables and 2.65 × 10⁻⁸ in others. Those differences change the answer by a few percent, which is small beside the effect of choosing the wrong gauge, but it explains why two calculators can give slightly different answers for the same wire. This tool uses 1.68 × 10⁻⁸ for copper and 2.82 × 10⁻⁸ for aluminium, both at 20 °C, and the note under the tool states the values it used.

The fourth mistake is ignoring temperature. Resistivity rises with temperature for metals: copper's resistance rises by about 0.393% per degree Celsius, so a copper conductor at 75 °C has roughly 22% more resistance than at 20 °C. Code tables such as NEC Chapter 9 Table 8 give resistance at 75 °C for that reason, and a drop calculated at 20 °C will understate the drop in a warm installation. This tool uses 20 °C values only, and the note under the tool says so.

The fifth mistake is treating the voltage drop as the whole story. A wire can pass the voltage-drop check and still be the wrong choice, because drop is not the same as ampacity: the current a wire can safely carry depends on insulation temperature rating, grouping, installation method and local codes, and this calculator does not check any of those. A wire that drops little voltage can still overheat if it is overloaded, and a wire that drops too much voltage is a sign to look again, not a full answer. The tool reports resistance, drop and power lost only.

The sixth mistake is expecting this calculator to cover alternating current or three-phase work. It gives DC resistance only. In AC circuits, skin effect pushes current towards the surface of the conductor and raises the effective resistance at higher frequencies, and reactance adds to the impedance. Three-phase voltage imbalance — where the three phase voltages are not equal — is a different calculation again, and this tool does not cover it. If the circuit is AC or three-phase, treat these figures as a DC starting point and use a calculation that fits the circuit.

What are the limits of this calculator?

This calculator gives DC resistance, voltage drop and power loss for a single uniform conductor at 20 °C, from the material, gauge, length and current entered. It does not model temperature change, skin effect, reactance, AC circuits, three-phase circuits, stranded versus solid construction, or resistance from splices, lugs, breakers, terminations and contact resistance. It does not check ampacity, overcurrent protection, grounding, termination temperature limits or any other code requirement. It does not say whether a wire size is suitable for a load or an installation, and it gives no advice on electrical work.

The figures are for planning and education only. Electrical work must follow local codes and be carried out by a qualified person. If a result will be used to choose a conductor for a real installation, check it against the manufacturer's data, the applicable code tables at the expected operating temperature, and the local rules for the installation. The resistivity values used here are standard published values at 20 °C and vary slightly with purity and temperature, as the gauge table section explains.

The tool also accepts a current of 0, which returns a drop of 0.000 V and a power loss of 0.00 W with the resistance figures unchanged. That is the correct result for a wire carrying no current, but a zero entry should still reflect a real condition rather than a blank left as zero. The tool does not store a result or report anything: everything runs in the browser, and nothing is uploaded.

How can I check the tool against a known result?

The simplest check uses the first test. Enter Copper, 12 AWG, one-way length 10 m, current 5 A, supply voltage 120 V. The tool should show a cross-sectional area of 3.3088 mm², a one-way resistance of 0.0508 Ω, a round-trip resistance of 0.1015 Ω, a one-way drop of 0.254 V, a round-trip drop of 0.508 V, a drop of 0.42% of supply, a power loss of 2.54 W, and a load voltage of 119.49 V.

A second check uses the custom area option. Enter Nichrome, Custom area 1.0 mm², one-way length 5 m, current 2 A, supply voltage 230 V. The tool should show a one-way resistance of 5.5000 Ω, a round-trip resistance of 11.0000 Ω, a round-trip drop of 22.000 V, a drop of 9.57% of supply, a power loss of 44.00 W, and a load voltage of 208.00 V.

A third check uses a different material with no supply voltage. Enter Gold, 10 AWG, one-way length 1 m, current 1 A, and leave the supply voltage blank. The tool should show an area of 5.2612 mm², a one-way resistance of 0.0046 Ω, a round-trip resistance of 0.0093 Ω, a round-trip drop of 0.009 V, a power loss of 0.01 W, and a dash in both the percentage box and the load voltage box.

A fourth check tests the errors. Enter a one-way length of 0 and the tool should show the error "The one-way wire length must be above 0." with no results. Choose Custom area, leave the area blank, and the tool should show the error "Please enter the cross-sectional area in square millimetres." with no results. Leave the current blank and the tool should show the error "Please enter the current in amperes." with no results. Enter a current of −2 and the tool should show the error "The current cannot be below 0." with no results.

The formula behind the tool is the standard resistivity relation, and the resistivity values are the published 20 °C figures listed in the Physics LibreTexts resistivity table. For the related calculation of a known resistance value, see the Ohms Law Calculator, and for the colour bands on a resistor, see the resistor colour code calculator. More tools in the same collection are in the calculators category.

Frequently asked questions

What is the formula for resistance in a wire?

The resistance of a uniform wire is R = ρL/A, where ρ is the resistivity of the material in ohm-metres, L is the length in metres, and A is the cross-sectional area in square metres. A longer wire resists more, a thicker wire resists less, and a material with a higher resistivity resists more at the same length and area. This tool applies that formula, then uses Ohm's law on the result to give voltage drop and power lost.

How do I calculate voltage drop in a wire?

First work out the wire's resistance from R = ρL/A. Then multiply by the current: V = I × R. For an ordinary two-conductor circuit, double the one-way length first, because the current travels out along one conductor and back along the other. To express the drop as a percentage, divide the round-trip drop by the supply voltage and multiply by 100. For example, a copper 12 AWG wire 10 m long carrying 5 A has a round-trip resistance of 0.1015 ohms, a drop of 0.508 V, and on a 120 V supply that is 0.42%.

What is the resistance of 12 AWG copper wire?

At 20 °C, 12 AWG copper wire is 0.5077 ohms per 100 metres, or 5.08 milliohms per metre. Its diameter is 2.053 mm and its cross-sectional area is 3.309 mm². The figure depends on the resistivity value used: with annealed copper at 1.724 × 10⁻⁸ ohm-metres instead of 1.68 × 10⁻⁸, the same wire is 0.5210 ohms per 100 metres. Resistance also rises with temperature, so code tables that give values at 75 °C are higher again.

How much voltage drop is acceptable?

The National Electrical Code gives its guidance in informational notes at 210.19 and 215.2: conductors sized to keep the drop to 3% on a branch circuit, and 5% in total from the service entrance to the farthest outlet, will provide reasonable efficiency of operation. Those figures are recommendations, not enforceable requirements, and some local jurisdictions adopt them as enforceable amendments. In volts, 3% and 5% are 3.6 V and 6.0 V on a 120 V circuit, and 7.2 V and 12.0 V on a 240 V circuit. This page gives no advice on whether a particular installation follows local codes.

Why does aluminium wire have more resistance than copper?

Because aluminium's resistivity is higher: 2.82 × 10⁻⁸ ohm-metres against copper's 1.68 × 10⁻⁸ at 20 °C. At the same gauge, an aluminium wire has about 68% more resistance than a copper wire, and it drops about 68% more voltage at the same current and length. To match a copper wire's resistance, an aluminium wire needs about 68% more cross-sectional area, which is why aluminium wiring is usually one or two gauges thicker than the copper wire it replaces.

Does this calculator work for AC circuits and three-phase loads?

No. It gives DC resistance only, from R = ρL/A. In AC circuits, skin effect raises the effective resistance at higher frequencies and reactance adds to the impedance, so the DC figure understates the real behaviour. Three-phase voltage imbalance, where the three phase voltages are not equal, is a different calculation and is not covered here. For AC or three-phase work, treat these figures as a DC starting point and use a calculation that fits the circuit.